GENO-Neutra type FNH-420-R This pH-value controlled system GENO-Neutra FNH-420-R is designed for neutralisation (increase of pH value to more than 6,5) of condensed water from gas and oil burning heat generators (condensing boilers) and/or exhaust systems made of aluminium, stainless steel, plastic, glass and ceramics acc. to the working sheet ATV-DVWK-A 251 and the DVGW test requirements System design: 1 Neutralisation system Neutra FNH-420-R as compact system consisting of: 1 Neutralisation tank for floor installation 1 Condensate inlet filter system 3,5 liter activated carbon filling 1 Circulation pump with integrated dosing valve 1 Distribution line Technic console with 1 pH-Electrode 1 Level probe with 4 switch levels 1 Feed pump with check valve 1 "GENO®-Neutra-matic" for control of neutralisation system with 2-line- display for monitoring an adjustment of operating parameter pH-value, pH-min alarm, pH-max alarm, tank shut-off with voltage-free alarm signal output. Removable cover 1 GENODOS®-dosing pump with console for fitting on wall or floor 1 Connection set for dosing pump 2 Hose clip 25mm with union nut 1" 1 Closing cap 1" 3,5 m Dosing hose 1 Suction pipe with integrated empty signal and pre-warning 1 Calibration solution pH 7 1 Calibration solution pH 4 6 m Outlet hose di=12mm 5 m Hose reinforced di=25mm complete packed in carton Technical data: Max. neutralisation capacity: 420 l/h Connection inlet : 25 DN overflow : 25 DN outlet : 12 DN Height inlet-/overflow : 105 mm Max. delivery height : 3 m Backwater ehight : 115 mm max. condensate-temperature : 40°C temporary : 50°C Power supply : 230V,50 Hz Protective system : IP 54 dimensions L/D/H mm] : 600/400/365 Make : Grünbeck Subject to technical modifications